How to apply limited export to the grid via Fusion Solar WEB and Fusion Solar APP
Introduction
This article explores a method for limiting power export to the grid through remote or local configuration using the Fusion Solar WEB portal or Fusion Solar APP. By following a simple procedure, users can ensure compliance with regulations and optimize energy usage. Let's dive into the steps and unlock the potential of remote grid management.
Prerequisites
- The smart meter is connected to the system
- You logged in as an Installer to the Fusion Solar WEB platform
Situation 1: Configuration remotely via Fusion Solar WEB portal |
Step 1: Choose
Step 2: Choose
Step 3: Choose
Situation 2: Configuration via Smart Logger WEB UI |
Step 1: Log in to the Smart Logger WEB UI > click Settings
Step 2: Go to Power Adjustment > Active Power Control > set Active power control mode as Export Limitation (kW) > select Limitation mode > set Maximum grid feed-in power as required by the grid operator > click Submit
Situation 3: Configuration locally via an inverter in the scenario with Smart Dongle using Fusion Solar APP |
Step 1: Log in to the inverter as Installer > select Power Adjustment > Active power control
Step 2: Select Active power > set Control Mode as Limited feed-in (kW) > set Limitation mode > set Maximum grid feed-in power as required by the grid operator
Situation 4: Configuration locally via Smart Logger using Fusion Solar APP |
Step 1: Go to Power Adjustment > Active Power Control
Step 2: Set Active power control mode as Limited feed-in (kW) > set Start Control to Yes > select Limitation mode > set Maximum grid feed-in power as required by the grid operator