Smart I-V Curve Diagnosis
The smart I-V curve diagnosis function allows you to check the health status of strings for the inverters connected to the NetEco 1000S.
Prerequisites
- You have logged in to the NetEco 1000S as the installer.
- You have added a device to the NetEco 1000S and the device state is normal.
- The inverter license controls the smart I-V curve diagnosis function. To ensure that smart I-V curve diagnosis works properly, perform scheduled inspection and import the inverter license file.
- It is recommended that the modules in an array have the same cleaning status in a diagnosis task.
- During the diagnosis, the irradiance must be greater than 600 W/㎡. Otherwise, the scan may fail on some PV strings, affecting the consistency of scan results.
- You are advised to clean the PV modules before the diagnosis to ensure that the test data reflects the actual status of the PV modules.
- You are advised to perform the diagnosis between 11:00 and 13:00 to avoid shading.
- The PV modules in the same array have an identical type and model. Every PV string has the same number of PV modules connected in series.
- Currently, the supported type of PV modules is common mono crystalline silicon or common polycrystalline silicon.
Procedure
- Choose Monitor > select one inverter > Settings > String details setup > fill the requested data for your PV panel installed > OK. If the configuration is the same for all inverters, click Batch Apply.
NOTE:
Skip this step if you already configured string details. -
Choose Maintenance > Device License Management > Upload License > Browse the file from your computer and Upload
NOTE:
If you don't have the device license, go to License Application > select devices > Export License Application File and send it to your distributor to get the license file. -
After you upload the license select Load License>Load all and Confirm
- Choose Maintenance > Smart I-V Curve Diagnosis from the main menu.
- Click Start Scanning > Setup the task (see parameters below) > click Save.
Task type:
Task On Plant-Level The health check applies to strings for all inverters connected to a PV plant.
Task On Inverter-Level The health check applies to all strings for an inverter.
PV plant:
In the PV plant area, select the SmartLoggers or inverters to be scanned.
An unlimited number of SmartLoggers can be scanned simultaneously.
A maximum of 100 inverters can be scanned simultaneously.
Cleaning status:
Specifies the cleaning status of a string. Select a value as required.
Environmental data:
Auto The system will automatically calculate the values of Irradiance and Temperature of panel.
Manually You need to manually enter the values of Irradiance and Temperature of panel. -
After a task is set, smart I-V curve diagnosis starts immediately:
-
To view the diagnosis result click under Operation column. The diagnosis task execution result is displayed:
- Click Read The Details. The diagnosis details are displayed:
- To query the intelligent diagnostic report go to Smart I-V Curve Diagnosis > click .
The Diagnostic Report page is displayed:
- Query Information of Task: The basic information of the string diagnosis task is displayed.
- Query Overview on Diagnosis: The pie chart and detailed information of the diagnosis result are displayed
- Query List Of Defective Strings: Information of all defective strings is displayed
-
To export the Report go to Smart I-V Curve Diagnosis > click > select the reports to be exported as required, and click OK.