Synchronizing Historical Performance Data
If there is no performance data of a device on the NetEco1000S because the device is disconnected for more than 6 hours and historical performance data cannot be automatically synchronized or the device logs have been obtained on the WebUI of the SmartLogger, you can create a synchronization task on the NetEco 1000S to synchronize the historical performance data of the device to the NetEco 1000S.
Prerequisites
- You have logged in to the NetEco 1000S as the installer.
- You have added a device to the NetEco 1000S and the device state is normal.
- If a device is connected to the NetEco 1000S through the SmartLogger, the SmartLogger version must be SmartLogger1000 V100R001C91 or later.
Context
- The SmartLogger saves historical performance data of the latest one month.
- The inverter saves historical performance data of the latest one year.
- The optimizer saves historical performance data of the latest two days.
The synchronization on the NetEco 1000S succeeds only when the SmartLogger, the inverter directly connected to the NetEco 1000S, or the optimizer stores historical performance data that needs to be synchronized.
Procedure
-
- Choose Historical Data > Synchronize Historical Data > Data Synchronization
- On the Data Synchronization tab page, click Create Synchronization Task > Choose a device for which you want to create a supplementary collection task from the device navigation tree > set the time range as required.The time range can be set to Today, Last three Days, Last seven Days, Last thirty Days, or Customize > OK. The supplementary collection task is performed automatically after the task is created.
- Click OK.The supplementary collection task is performed automatically after the task is created.
- Choose Historical Data > Synchronize Historical Data > Data Synchronization
Follow-up Procedure
If the supplementary collection task fails to be executed, click to execute the task again.